Back to overview

CVE-2017-14469

CRITICAL
10.0
CVSS 3.0
Description
An exploitable access control vulnerability exists in the data, program, and function file permissions functionality of Allen Bradley Micrologix 1400 Series B FRN 21.2 and before. A specially crafted packet can cause a read or write operation resulting in disclosure of sensitive information, modification of settings, or modification of ladder logic. An attacker can send unauthenticated packets to trigger this vulnerability. Required Keyswitch State: REMOTE or PROG Associated Fault Code: 0028 Fault Type: Non-User Description: Values 0x01 and 0x02 are invalid values for the user fault routine. By writing directly to the file it is possible to set these values. When this is done and the device is moved into a run state, a fault is triggered. NOTE: This is not possible through RSLogix.

Metadata

CVE ID
CVE-2017-14469
State
PUBLISHED
Assigner
talos
Reserved
2017-09-13 00:00 UTC
Published
2018-04-05 21:00 UTC
Last updated
2024-09-16 17:48 UTC
Vendor / Product
Talos / Allen Bradley
Sources
cve.org  ·  NVD

Severity & Metrics

10.0 CRITICAL CVSS 3.0
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
Affected products (1)
VendorProductPlatformVersions
Talos Allen Bradley Allen Bradley Micrologix 1400 Series B FRN 21.2, Allen Bradley Micrologix 1400 Series B FRN 21.0, Allen Bradley Micrologix 1400 Series B FRN 15
Weakness (CWE)
CWESourceDescription
cna denial of service
CVSS scores (1)
ScoreSeverityVersionSourceVector
10.0 CRITICAL 3.0 cna CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
Back to overview