CVE-2026-3611
CRITICAL
10.0
CVSS 3.1
Description
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Metadata
Severity & Metrics
10.0
CRITICAL CVSS 3.1
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H
SSVC — CISA Coordinator
Affected products (7)
| Vendor | Product | Platform | Versions |
|---|---|---|---|
| Honeywell | IQ3 | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
| Honeywell | IQ412 | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
| Honeywell | IQ41x | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
| Honeywell | IQ422 | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
| Honeywell | IQ4E | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
| Honeywell | IQ4NC | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
| Honeywell | IQECO | — | v3.50_3.44 ≤ 4.36 (build 4.3.7.9) |
Weakness (CWE)
| CWE | Source | Description |
|---|---|---|
| CWE-306 | cna | CWE-306 Missing authentication for critical function |
CVSS scores (2)
| Score | Severity | Version | Source | Vector |
|---|---|---|---|---|
| 10.0 | CRITICAL | 4.0 | cna | CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H |
| 10.0 | CRITICAL | 3.1 | cna | CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H |
References (3)